240-Cell Modular 20 year VRLA AGM High-Rate Battery Systems for Datacenter Standby Applictions

Datacenter High-Rate Discharge (heavy load for short duration)

*** ALL RATINGS ARE BASED ON 240-CELL BATTERY SYSTEMS (480vdc NOMINAL) ***

CONTACT SPECIFIED POWER FOR SYSTEM MODEL NUMBER, DIMENSIONS, WEIGHTS, SHIPMENT SIZE, LEAD TIME, PRICING, DRAWINGS AND COMPLETE PROJECT SUBMITTALS

Mfc Series Specified Power System Reference Number kwB 5min kwB 10min kwB 15min EOL kwB 5min EOL kwB 10min EOL kwB 15min
HBL STHP 120-1300-100100 73.4 61.2 52.8 58.8 49.0 42.2
East Penn Unigy II (NIL) 102-1080-100224 74.9 65.0 56.2 59.9 52.0 44.9
East Penn Unigy II (ILM) 102-1080-104624 74.9 65.0 56.2 59.9 52.0 44.9
GNB Absolyte 115-1690-113600 81.8 68.6 57.8 65.5 54.9 46.3
East Penn Unigy II (NIL) 102-1080-101724 86.9 77.0 69.1 69.5 61.6 55.3
East Penn Unigy II (ILM) 102-1080-106124 86.9 77.0 69.1 69.5 61.6 55.3
EnerSys DDM 103-1110-197099 103.7 84.0 70.1 82.9 67.2 56.1
HBL STHP 120-1300-100200 109.9 91.9 79.4 87.9 73.5 63.6
East Penn Unigy II (NIL) 102-1080-100324 112.3 97.4 84.0 89.9 78.0 67.2
East Penn Unigy II (ILM) 102-1080-104724 112.3 97.4 84.0 89.9 78.0 67.2
East Penn Unigy II (ILM) 102-1080-109324 112.3 97.4 84.0 89.9 78.0 67.2
GNB Absolyte 115-1690-113700 122.9 103.0 86.9 98.3 82.4 69.5
East Penn Unigy II (ILM) 102-1080-106224 130.1 115.4 103.7 104.1 92.4 82.9
East Penn Unigy II (NIL) 102-1080-101824 130.1 115.4 103.7 104.1 92.4 82.9
HBL STHP 120-1300-100300 146.6 122.4 105.8 117.3 97.9 84.7
EnerSys DDM 103-1110-197100 150.2 129.4 114.5 120.2 103.5 91.6
East Penn Unigy II (ILM) 102-1080-104824 149.8 130.1 112.6 119.8 104.1 90.0
East Penn Unigy II (NIL) 102-1080-100424 149.8 130.1 112.6 119.8 104.1 90.0
GNB Absolyte 115-1690-113800 163.9 137.5 115.9 131.1 110.0 92.7
GNB Absolyte 115-1690-114000 161.0 142.3 127.0 128.8 113.9 101.6
East Penn Unigy II (NIL) 102-1080-103224 162.3 146.2 133.0 129.8 116.9 106.4
East Penn Unigy II (ILM) 102-1080-107624 162.3 146.2 133.0 129.8 116.9 106.4
HBL STHP 120-1300-100400 183.4 153.1 132.2 146.7 122.5 105.8
East Penn Unigy II (ILM) 102-1080-106324 173.5 154.3 138.5 138.8 123.5 110.8
East Penn Unigy II (NIL) 102-1080-101924 173.5 154.3 138.5 138.8 123.5 110.8
East Penn Unigy II (NIL) 102-1080-100524 187.4 162.7 140.4 150.0 130.2 112.3
East Penn Unigy II (ILM) 102-1080-104924 187.4 162.7 140.4 150.0 130.2 112.3
C&D Technologies MS Endur 101-1220-121200 189.8 175.2 160.6 151.9 140.2 128.4
HBL STHP 120-1300-100500 220.1 183.6 158.6 176.1 146.9 126.9
GNB Absolyte 115-1690-114100 214.8 189.8 169.4 171.8 151.9 135.6
East Penn Unigy II (ILM) 102-1080-106424 216.7 192.5 172.8 173.4 154.0 138.2
East Penn Unigy II (NIL) 102-1080-102024 216.7 192.5 172.8 173.4 154.0 138.2
EnerSys DDM 103-1110-197200 225.4 194.2 171.8 180.3 155.3 137.5
East Penn Unigy II (NIL) 102-1080-103324 216.4 194.9 177.3 173.1 155.9 141.8
East Penn Unigy II (ILM) 102-1080-107724 216.4 194.9 177.3 173.1 155.9 141.8
East Penn Unigy II (NIL) 102-1080-100624 225.4 195.1 168.7 180.3 156.1 135.0
East Penn Unigy II (ILM) 102-1080-105024 225.4 195.1 168.7 180.3 156.1 135.0
GNB Absolyte 115-1690-113900 245.8 206.2 174.0 196.6 164.9 139.2
HBL STHP 120-1300-100600 256.6 214.3 185.3 205.2 171.5 148.2
East Penn Unigy II (NIL) 102-1080-100724 250.1 227.8 196.6 200.1 182.2 157.2
East Penn Unigy II (ILM) 102-1080-105124 250.1 227.8 196.6 200.1 182.2 157.2
East Penn Unigy II (ILM) 102-1080-106524 250.1 231.4 207.6 200.1 185.1 166.1
East Penn Unigy II (NIL) 102-1080-102124 250.1 231.4 207.6 200.1 185.1 166.1
C&D Technologies MS Endur 101-1220-121400 253.2 233.5 214.1 202.6 186.8 171.3
GNB Absolyte 115-1690-114200 268.6 237.1 211.7 214.8 189.7 169.3
East Penn Unigy II (NIL) 102-1080-103424 270.4 243.6 221.6 216.3 194.9 177.3
East Penn Unigy II (ILM) 102-1080-107824 270.4 243.6 221.6 216.3 194.9 177.3
HBL STHP 120-1300-100700 293.3 245.0 211.7 234.6 196.0 169.3
East Penn Unigy II (NIL) 102-1080-102224 250.1 250.1 242.2 200.1 200.1 193.7
East Penn Unigy II (ILM) 102-1080-106624 250.1 250.1 242.2 200.1 200.1 193.7
EnerSys DDM 103-1110-197300 300.2 258.7 229.0 240.2 207.0 183.2
East Penn Unigy II (ILM) 102-1080-105224 299.5 260.2 224.6 239.6 208.1 179.7
East Penn Unigy II (NIL) 102-1080-100824 299.5 260.2 224.6 239.6 208.1 179.7
HBL STHP 120-1300-100800 330.0 275.5 238.1 264.0 220.4 190.5
EnerSys DDM 103-1110-197400 311.8 279.6 253.0 249.4 223.7 202.4
GNB Absolyte 115-1690-114300 322.1 284.6 254.2 257.7 227.7 203.3
C&D Technologies MS Endur 101-1220-121600 316.3 292.1 267.6 253.1 233.7 214.1
East Penn Unigy II (NIL) 102-1080-103524 324.5 292.4 266.0 259.6 233.9 212.8
East Penn Unigy II (ILM) 102-1080-107924 324.5 292.4 266.0 259.6 233.9 212.8
East Penn Unigy II (NIL) 102-1080-100924 337.0 292.8 252.7 269.6 234.2 202.2
East Penn Unigy II (ILM) 102-1080-105324 337.0 292.8 252.7 269.6 234.2 202.2
HBL STHP 120-1300-100900 366.7 306.2 264.5 293.4 245.0 211.6
East Penn Unigy II (ILM) 102-1080-106724 347.3 308.4 276.7 277.8 246.7 221.4
East Penn Unigy II (NIL) 102-1080-102324 347.3 308.4 276.7 277.8 246.7 221.4
GNB Absolyte 115-1770-133100 360.0 313.7 277.9 288.0 250.9 222.3
East Penn Unigy II (ILM) 102-1080-105424 374.4 325.2 280.8 299.5 260.2 224.6
East Penn Unigy II (NIL) 102-1080-101024 374.4 325.2 280.8 299.5 260.2 224.6
EnerSys DDM 103-1110-194300 363.8 326.4 295.2 291.1 261.1 236.2
GNB Absolyte 115-1690-114400 375.8 332.2 296.4 300.7 265.7 237.1
C&D Technologies MS Endur 101-1220-121800 363.4 335.3 309.1 290.7 268.2 247.3
HBL STHP 120-1300-101000 403.4 336.7 290.9 322.8 269.4 232.7
East Penn Unigy II (NIL) 102-1080-103624 378.6 341.1 310.3 302.9 272.9 248.2
East Penn Unigy II (ILM) 102-1080-108024 378.6 341.1 310.3 302.9 272.9 248.2
East Penn Unigy II (NIL) 102-1080-102424 390.5 346.8 311.3 312.4 277.4 249.0
East Penn Unigy II (ILM) 102-1080-106824 390.5 346.8 311.3 312.4 277.4 249.0
East Penn Unigy II (ILM) 102-1080-105524 411.8 357.8 308.9 329.5 286.3 247.1
East Penn Unigy II (NIL) 102-1080-101124 411.8 357.8 308.9 329.5 286.3 247.1
GNB Absolyte 115-1770-133200 420.0 366.0 324.2 336.0 292.8 259.4
HBL STHP 120-1300-101100 440.2 367.4 317.3 352.1 294.0 253.8
East Penn Unigy II (ILM) 102-1080-106924 433.9 385.4 346.1 347.1 308.4 276.9
East Penn Unigy II (NIL) 102-1080-102524 433.9 385.4 346.1 347.1 308.4 276.9
East Penn Unigy II (ILM) 102-1080-108124 432.7 389.8 354.6 346.2 311.8 283.7
East Penn Unigy II (NIL) 102-1080-103724 432.7 389.8 354.6 346.2 311.8 283.7
East Penn Unigy II (NIL) 102-1080-101224 449.3 390.2 337.0 359.4 312.2 269.6
East Penn Unigy II (ILM) 102-1080-105624 449.3 390.2 337.0 359.4 312.2 269.6
HBL STHP 120-1300-101200 476.6 398.2 343.7 381.3 318.5 274.9
C&D Technologies MS Endur 101-1220-122000 443.0 409.0 374.6 354.4 327.2 299.7
HBL STHP 120-1300-101300 498.7 416.4 359.8 399.0 333.1 287.8
GNB Absolyte 115-1770-133300 480.0 418.3 370.6 384.0 334.7 296.4
East Penn Unigy II (ILM) 102-1080-105724 486.7 422.9 365.0 389.4 338.3 292.0
East Penn Unigy II (NIL) 102-1080-101324 486.7 422.9 365.0 389.4 338.3 292.0
East Penn Unigy II (ILM) 102-1080-107024 477.1 423.8 380.4 381.7 339.1 304.3
East Penn Unigy II (NIL) 102-1080-102624 477.1 423.8 380.4 381.7 339.1 304.3
East Penn Unigy II (NIL) 102-1080-103824 486.8 438.6 399.0 389.4 350.8 319.2
East Penn Unigy II (ILM) 102-1080-108224 486.8 438.6 399.0 389.4 350.8 319.2
East Penn Unigy II (ILM) 102-1080-105824 524.2 455.3 393.1 419.3 364.2 314.5
East Penn Unigy II (NIL) 102-1080-101424 524.2 455.3 393.1 419.3 364.2 314.5
East Penn Unigy II (ILM) 102-1080-107124 500.2 462.5 415.2 400.1 370.0 332.2
East Penn Unigy II (NIL) 102-1080-102724 500.2 462.5 415.2 400.1 370.0 332.2
HBL STHP 120-1300-101400 557.5 465.4 402.0 446.0 372.3 321.6
EnerSys DDM 103-1110-194400 519.8 466.1 421.7 415.9 372.9 337.3
C&D Technologies MS Endur 101-1220-115200 506.4 467.3 428.2 405.1 373.8 342.5
GNB Absolyte 115-1770-133400 540.0 470.6 416.9 432.0 376.5 333.5
East Penn Unigy II (ILM) 102-1080-108324 540.9 487.3 443.3 432.7 389.8 354.6
East Penn Unigy II (NIL) 102-1080-103924 540.9 487.3 443.3 432.7 389.8 354.6
East Penn Unigy II (ILM) 102-1080-105924 561.6 487.9 421.2 449.3 390.3 337.0
East Penn Unigy II (NIL) 102-1080-101524 561.6 487.9 421.2 449.3 390.3 337.0
East Penn Unigy II (ILM) 102-1080-107224 500.2 500.2 449.8 400.1 400.1 359.8
East Penn Unigy II (NIL) 102-1080-102824 500.2 500.2 449.8 400.1 400.1 359.8
East Penn Unigy II (NIL) 102-1080-101624 599.0 520.3 449.3 479.2 416.3 359.4
East Penn Unigy II (ILM) 102-1080-106024 599.0 520.3 449.3 479.2 416.3 359.4
HBL STHP 120-1300-101500 623.5 520.6 449.5 498.8 416.4 359.6
GNB Absolyte 115-1770-133500 600.0 523.0 463.4 480.0 418.4 370.8
C&D Technologies MS Endur 101-1220-122400 569.5 525.6 481.7 455.6 420.5 385.3
EnerSys DDM 103-1110-194800 588.0 528.2 478.8 470.4 422.6 383.0
East Penn Unigy II (NIL) 102-1080-104024 595.0 536.0 487.6 476.0 428.8 390.1
East Penn Unigy II (ILM) 102-1080-108424 595.0 536.0 487.6 476.0 428.8 390.1
East Penn Unigy II (ILM) 102-1080-107324 607.7 539.8 484.6 486.1 431.8 387.6
East Penn Unigy II (NIL) 102-1080-102924 607.7 539.8 484.6 486.1 431.8 387.6
EnerSys DDM 103-1110-194500 623.5 559.4 505.9 498.8 447.6 404.7
HBL STHP 120-1300-101600 678.5 566.4 489.4 542.8 453.1 391.5
GNB Absolyte 115-1770-133600 660.0 575.0 509.8 528.0 460.0 407.8
East Penn Unigy II (NIL) 102-1080-103024 651.4 577.9 518.9 521.1 462.3 415.1
East Penn Unigy II (ILM) 102-1080-107424 651.4 577.9 518.9 521.1 462.3 415.1
C&D Technologies MS Endur 101-1220-122600 632.9 584.2 535.2 506.3 467.3 428.2
East Penn Unigy II (ILM) 102-1080-108524 649.1 584.7 531.9 519.2 467.8 425.5
East Penn Unigy II (NIL) 102-1080-104124 649.1 584.7 531.9 519.2 467.8 425.5
EnerSys DDM 103-1110-194600 675.6 606.0 547.9 540.5 484.8 438.3
HBL STHP 120-1300-101700 733.4 612.5 529.0 586.8 490.0 423.2
East Penn Unigy II (NIL) 102-1080-103124 694.3 616.8 553.7 555.5 493.4 442.9
East Penn Unigy II (ILM) 102-1080-107524 694.3 616.8 553.7 555.5 493.4 442.9
GNB Absolyte 115-1770-133700 720.0 627.4 556.1 576.0 501.9 444.9
CSB STMU 105-1330-101400 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-101300 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-101200 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-101100 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-100500 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-100400 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-100300 733.9 627.6 549.8 587.1 502.1 439.9
CSB STMU 105-1330-100200 733.9 627.6 549.8 587.1 502.1 439.9
East Penn Unigy II (NIL) 102-1080-104224 703.2 633.5 576.2 562.5 506.8 461.0
East Penn Unigy II (ILM) 102-1080-108624 703.2 633.5 576.2 562.5 506.8 461.0
EnerSys DDM 103-1110-194900 705.6 633.8 574.6 564.5 507.1 459.6
C&D Technologies MS Endur 101-1220-122800 696.2 642.5 588.5 557.0 514.0 470.8
HBL STHP 120-1300-101800 806.9 673.7 581.8 645.5 538.9 465.4
HBL STHP 120-1300-101750 806.9 673.7 581.8 645.5 538.9 465.4
GNB Absolyte 115-1770-133800 780.0 679.7 602.4 624.0 543.7 481.9
East Penn Unigy II (ILM) 102-1080-108724 757.2 682.2 620.6 605.8 545.7 496.5
East Penn Unigy II (NIL) 102-1080-104324 757.2 682.2 620.6 605.8 545.7 496.5
EnerSys DDM 103-1110-195000 764.4 686.6 622.3 611.5 549.3 497.9
C&D Technologies MS Endur 101-1220-123000 759.4 700.8 642.0 607.5 560.6 513.6
East Penn Unigy II (ILM) 102-1080-108824 811.3 730.9 664.9 649.1 584.7 531.9
East Penn Unigy II (NIL) 102-1080-104424 811.3 730.9 664.9 649.1 584.7 531.9
GNB Absolyte 115-1770-133900 840.0 732.0 648.7 672.0 585.6 519.0
HBL STHP 120-1300-101850 880.1 734.9 634.8 704.1 587.9 507.8
HBL STHP 120-1300-101900 880.1 734.9 634.8 704.1 587.9 507.8
EnerSys DDM 103-1110-194700 831.6 745.9 674.4 665.3 596.7 539.5
C&D Technologies MS Endur 101-1220-123200 822.7 759.4 695.5 658.2 607.5 556.4
HBL STHP 120-1300-101950 916.8 765.6 661.2 733.4 612.5 529.0
HBL STHP 120-1300-102000 916.8 765.6 661.2 733.4 612.5 529.0
East Penn Unigy II (NIL) 102-1080-104524 865.4 779.6 709.2 692.3 623.7 567.4
East Penn Unigy II (ILM) 102-1080-108924 865.4 779.6 709.2 692.3 623.7 567.4
GNB Absolyte 115-1770-134000 900.0 784.3 695.0 720.0 627.5 556.0
EnerSys DDM 103-1110-195200 891.8 805.9 737.0 713.5 644.7 589.6
C&D Technologies MS Endur 101-1220-123400 886.1 817.7 749.0 708.9 654.1 599.2
HBL STHP 120-1300-102100 997.4 832.8 719.3 798.0 666.2 575.4
GNB Absolyte 115-1770-134100 960.0 836.6 741.4 768.0 669.3 593.1
EnerSys DDM 103-1110-195100 940.8 845.3 766.1 752.6 676.2 612.9
EnerSys DDM 103-1110-195300 966.2 873.1 798.2 773.0 698.5 638.6
HBL STHP 120-1300-102200 1056.2 881.8 761.5 845.0 705.4 609.2
HBL STHP 120-1300-102300 1100.2 918.5 793.4 880.1 734.8 634.8
CSB STMU 105-1330-102600 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102900 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102800 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102700 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102100 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102500 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102200 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102400 1100.9 941.3 824.9 880.7 753.0 659.9
CSB STMU 105-1330-102300 1100.9 941.3 824.9 880.7 753.0 659.9
HBL STHP 120-1300-102400 1173.6 979.9 846.2 938.9 783.9 677.0
HBL STHP 120-1300-102500 1246.8 1041.1 899.0 997.4 832.9 719.2
GNB Absolyte 115-1830-103600 5min N/A 1070.9 975.1 5min N/A 856.7 780.1
EnerSys DDM 103-1110-195400 1189.2 1074.5 982.6 951.4 859.6 786.0
HBL STHP 120-1300-102600 1357.0 1133.0 978.5 1085.6 906.4 782.8
HBL STHP 120-1300-102700 1466.9 1224.7 1057.9 1173.5 979.8 846.3
HBL STHP 120-1300-102750 1613.5 1347.4 1163.5 1290.8 1077.9 930.8
HBL STHP 120-1300-102800 1613.5 1347.4 1163.5 1290.8 1077.9 930.8
HBL STHP 120-1300-102850 1723.7 1439.0 1243.0 1378.9 1151.2 994.4
HBL STHP 120-1300-102900 1723.7 1439.0 1243.0 1378.9 1151.2 994.4
HBL STHP 120-1300-102950 1833.6 1531.0 1322.4 1466.9 1224.8 1057.9
HBL STHP 120-1300-103000 1833.6 1531.0 1322.4 1466.9 1224.8 1057.9
GNB Absolyte 115-1830-103700 5min N/A 1606.1 1462.8 5min N/A 1284.9 1170.2
HBL STHP 120-1300-103100 1943.5 1622.9 1401.6 1554.8 1298.3 1121.3
HBL STHP 120-1300-103200 2053.7 1714.8 1481.0 1642.9 1371.8 1184.8
HBL STHP 120-1300-103300 2200.3 1837.2 1586.6 1760.3 1469.8 1269.3
HBL STHP 120-1300-103400 2347.0 1959.6 1692.5 1877.6 1567.7 1354.0
HBL STHP 120-1300-103500 2567.0 2143.4 1851.1 2053.6 1714.8 1480.9
HBL STHP 120-1300-103450 2567.0 2143.4 1851.1 2053.6 1714.8 1480.9
HBL STHP 120-1300-103600 2933.8 2449.7 2115.6 2347.0 1959.7 1692.5
HBL STHP 120-1300-103700 3153.8 2633.3 2274.2 2523.1 2106.6 1819.4
HBL STHP 120-1300-103800 3300.5 2755.7 2380.1 2640.4 2204.5 1904.1
HBL STHP 120-1300-103900 3667.2 3061.9 2644.6 2933.8 2449.5 2115.6
HBL STHP 120-1300-104000 4033.9 3368.2 2909.0 3227.1 2694.5 2327.2
HBL STHP 120-1300-104100 4254.0 3551.8 3067.7 3403.2 2841.4 2454.1
HBL STHP 120-1300-104200 4400.6 3674.2 3173.5 3520.5 2939.3 2538.8