VRS12-155F

Lead-Acid AGM Medium Cycle – Medium Rate Moderate to Regular Cycling Stationary Batteries, 12V, 153.8 Ah (c20), Regulated Valve, lead-calcium grid plate

Description

Solar Multi-Cell VRLA Battery, AGM, Long Life low calcium thick proprietary pasted alloy grid plate, Polypropylene case, 12V with (2) 1/4-20 UNC (threaded insert) terminals [153.8Ah (c20)], 22.01″L x 4.95″W x 11.14″H (max ht), 115 Lbs

Additional information

Weight 115 lbs
Dimensions 22.01 × 4.95 × 11.14 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead-calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4-20 UNC (threaded insert)

Terminal Location

Front

BCI Reference

FT-SW-150

Length inches

22.01

Width inches

4.95

Height inches

11.14

Weight in Lbs

115

AH (c5)

126

AH (c8)

136.8

AH (c20)

153.8

50% DOD Cycle rating

1800

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Capacity Bracket (C100 Ah)

100 – 199 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Moderate to Regular Cycling

Common Applications

Renewable