2XDJC-09

Lead-Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 4V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

(Superseded, consider 2DJC-09HP) UPS / Switchgear & Control – High Rate Multi-Cell Flooded Lead-Acid Battery, Suspended Lead Calcium Plate, High Impact PVC case, 4V with (2) Hardened-Lead Flag Post terminals [Ah (c10), 191.2Ah (c8), 1.250 S.G.], 8.09″L x 13.58″W x 15.22″H (max ht), 77 Lbs

Additional information

Weight 77 lbs
Dimensions 8.09 × 13.58 × 15.22 in
Product Discontinued?

Yes

Availability

consider 2DJC-09HP, Superseded

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

High Impact PVC

Battery Valve Style

Vented

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Type

Hardened-Lead Flag Post

Terminal Location

Top

Length inches

8.09

Width inches

13.58

Height inches

15.22

Weight in Lbs

77

WPC (10min to 1.67vpc @ 25c)

620

WPC (15min to 1.67vpc @ 25c)

520

WPC (20min to 1.67vpc @ 25c)

452

240-cell kW rating (10min)

148.8

240-cell kW rating (15min)

124.8

240-cell kW rating (20min)

108.48

AH (c5)

180.5

AH (c8)

191.2

Capacity Bracket (10 Min WPC)

615 – 679 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems, Utility Switchgear and Control