AT-15P

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

ms Endur II, Multi Purpose Long Life – Multi Rate single cell VRLA / AGM battery used with multi-cell modules, Proprietary Lead Calcium Alloy Grid Plate, Polypropylene case, 2V, [839.2Ah (c8), 1.300 S.G.], 6.12″W x 23.19″D x 9.04″H (module ht), 150.25 Lbs

Additional information

Weight 150.25 lbs
Dimensions 6.12 × 9.04 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Location

Front

Width inches

6.12

Height inches

9.04

Depth inches

23.19

Weight in Lbs

150.25

WPC (10min to 1.67vpc @ 25c)

1704

WPC (15min to 1.67vpc @ 25c)

1561

WPC (20min to 1.67vpc @ 25c)

1427

240-cell kW rating (10min)

408.96

240-cell kW rating (15min)

374.64

240-cell kW rating (20min)

342.48

AH (c5)

770

AH (c8)

839.2

AH (c10)

863

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, Telecom, Utility Switchgear and Control