AT-21P

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

ms Endur II, Multi Purpose Long Life – Multi Rate single cell VRLA / AGM battery used with multi-cell modules, Proprietary Lead Calcium Alloy Grid Plate, Polypropylene case, 2V, [1148Ah (c8), 1.300 S.G.], 7.49″W x 23.19″D x 9.04″H (module ht), 186.25 Lbs

Additional information

Weight 186.25 lbs
Dimensions 7.49 × 9.04 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Location

Front

Width inches

7.49

Height inches

9.04

Depth inches

23.19

Weight in Lbs

186.25

WPC (10min to 1.67vpc @ 25c)

2434

WPC (15min to 1.67vpc @ 25c)

2230

WPC (20min to 1.67vpc @ 25c)

2039

240-cell kW rating (10min)

584.16

240-cell kW rating (15min)

535.2

240-cell kW rating (20min)

489.36

AH (c5)

1050

AH (c8)

1148

AH (c10)

1188

Capacity Bracket (10 Min WPC)

2265 – 2564 WPC (10 min)

Capacity Bracket (15 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (20 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, Telecom, Utility Switchgear and Control