E0965060CE01

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 120V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

ms Endur II (AT-9P6x5x2), Multi Purpose Long Life – Multi Rate modular VRLA battery string configured as 2 stacks of 5 modules, ea module w/ (6) VRLA series-connected cells per stackable steel module, Lead Calcium AGM, Polypropylene case, 120V, [892 wpc @ 15 min to 1.67vpc], [480Ah (c8), 1.300 S.G.], Individual Module dimensions = 27.86″W x 24.75″D x 52.2″H, total system weight = 6010 Lbs

Additional information

Weight 6010 lbs
Dimensions 27.86 × 52.2 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

60

Battery Nominal DC Volts

120

Terminal Location

Front

Width inches

27.86

Height inches

52.2

Depth inches

24.75

Weight in Lbs

6010

WPC (10min to 1.67vpc @ 25c)

973

WPC (15min to 1.67vpc @ 25c)

892

WPC (20min to 1.67vpc @ 25c)

816

240-cell kW rating (10min)

233.52

240-cell kW rating (15min)

214.08

240-cell kW rating (20min)

195.84

AH (c5)

440

AH (c8)

480

AH (c10)

496

Capacity Bracket (10 Min WPC)

915 – 989 WPC (10 min)

Capacity Bracket (15 Min WPC)

820 – 914 WPC (15 min)

Capacity Bracket (20 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Commercial Lighting Inverters, Data Center UPS Systems, Utility Switchgear and Control