6AVR75-19 (NIL)M3-012

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 820 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate battery string using multiple single cells contained in steel stackable modules, Lead Calcium VRLA AGM, 12vdc battery system [1297 WPC @15 min to 1.67vpc],[820Ah (c20), 740Ah (c10), 704Ah (c8)], 24.5″D x 24.15″W x 31.3024″H (max ht), 784 Lbs

Additional information

Weight 784 lbs
Dimensions 24.15 × 24.15 × 31.3024 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Location

Front

Length inches

24.15

Width inches

24.15

Height inches

31.3024

Depth inches

24.5

Weight in Lbs

784

WPC (10min to 1.67vpc @ 25c)

1445

WPC (15min to 1.67vpc @ 25c)

1297

WPC (20min to 1.67vpc @ 25c)

1184

240-cell kW rating (10min)

346.8

240-cell kW rating (15min)

311.28

240-cell kW rating (20min)

284.16

AH (c5)

635

AH (c8)

704

AH (c10)

740

AH (c20)

820

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control