Description
Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 6V module [2307 WPC @15 min to 1.67vpc],[1460Ah (c20), 1310Ah (c10), 1256Ah (c8)], 24.5″D x 39.9″W x 9.48″H (max ht), 649 Lbs
Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 6V, 1460 Ah (c20), Regulated Valve, lead calcium grid plate
Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 6V module [2307 WPC @15 min to 1.67vpc],[1460Ah (c20), 1310Ah (c10), 1256Ah (c8)], 24.5″D x 39.9″W x 9.48″H (max ht), 649 Lbs
| Weight | 649 lbs |
|---|---|
| Dimensions | 39.9 × 39.9 × 9.48 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0030 |
| Battery Chemistry | Lead-Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 3 |
| Battery Nominal DC Volts | 6 |
| Terminal Location | Front |
| Length inches | 39.9 |
| Width inches | 39.9 |
| Height inches | 9.48 |
| Depth inches | 24.5 |
| Weight in Lbs | 649 |
| WPC (10min to 1.67vpc @ 25c) | 2570 |
| WPC (15min to 1.67vpc @ 25c) | 2307 |
| WPC (20min to 1.67vpc @ 25c) | 2105 |
| 240-cell kW rating (10min) | 616.8 |
| 240-cell kW rating (15min) | 553.68 |
| 240-cell kW rating (20min) | 505.2 |
| AH (c5) | 1125 |
| AH (c8) | 1256 |
| AH (c10) | 1310 |
| AH (c20) | 1460 |
| 50% DOD Cycle rating | 1800 |
| Capacity Bracket (10 Min WPC) | 2565 – 2864 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 2265 – 2564 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 1965 – 2264 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 000 – 1, 1, 999 Ah (C8) |
| Capacity Bracket (C8 Ah) | 000 – 1, 1, 999 Ah (C8) |
| Capacity Bracket (C10 Ah) | 000 – 1, 1, 999 Ah (C10) |
| Capacity Bracket (C20 Ah) | 000 – 1, 1, 999 Ah (C20) |
| Capacity Bracket (C100 Ah) | 000 – 1, 1, 999 Ah (C100) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium-High |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Data Center UPS Systems, Telecom, Utility Switchgear and Control |