6AVR95-15 (NIL)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 790 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 12V module [1292.9 WPC @15 min to 1.67vpc],[790Ah (c20), 696Ah (c10), 664.8Ah (c8)], 27.12″D x 37″W x 9.48″H (max ht), 688 Lbs

Additional information

Weight 688 lbs
Dimensions 37 × 37 × 9.48 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Location

Front

Length inches

37

Width inches

37

Height inches

9.48

Depth inches

27.12

Weight in Lbs

688

WPC (10min to 1.67vpc @ 25c)

1421.2

WPC (15min to 1.67vpc @ 25c)

1292.9

WPC (20min to 1.67vpc @ 25c)

1187.5

240-cell kW rating (10min)

341.088

240-cell kW rating (15min)

310.296

240-cell kW rating (20min)

285

AH (c5)

600

AH (c8)

664.8

AH (c10)

696

AH (c20)

790

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control