6AVR75-7 (ILM)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 280 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, 12V module [432 WPC @15 min to 1.67vpc],[280Ah (c20), 250Ah (c10), 232Ah (c8)], 25.25″D x 19″W x 9.54″H (max ht), 314 Lbs

Additional information

Weight 314 lbs
Dimensions 19 × 19 × 9.54 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Location

Front

Length inches

19

Width inches

19

Height inches

9.54

Depth inches

25.25

Weight in Lbs

314

WPC (10min to 1.67vpc @ 25c)

481

WPC (15min to 1.67vpc @ 25c)

432

WPC (20min to 1.67vpc @ 25c)

395

240-cell kW rating (10min)

115.44

240-cell kW rating (15min)

103.68

240-cell kW rating (20min)

94.8

AH (c5)

210

AH (c8)

232

AH (c10)

250

AH (c20)

280

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

436 – 524 WPC (10 min)

Capacity Bracket (15 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (20 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Capacity Bracket (C100 Ah)

200 – 349 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control