60AVR95-13 (ILM)M6-025

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 120V, 678 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate battery string using multiple single cells contained in steel stackable modules, Lead Calcium VRLA AGM, 120vdc battery system [1108.2 WPC @15 min to 1.67vpc],[678Ah (c20), 596Ah (c10), 569.6Ah (c8)], 27.88″D x 65″W x 45.7″H (max ht), 6240 Lbs

Additional information

Weight 6240 lbs
Dimensions 65 × 65 × 45.7 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

60

Battery Nominal DC Volts

120

Terminal Location

Front

Length inches

65

Width inches

65

Height inches

45.7

Depth inches

27.88

Weight in Lbs

6240

WPC (10min to 1.67vpc @ 25c)

1218.2

WPC (15min to 1.67vpc @ 25c)

1108.2

WPC (20min to 1.67vpc @ 25c)

1017.9

240-cell kW rating (10min)

292.368

240-cell kW rating (15min)

265.968

240-cell kW rating (20min)

244.296

AH (c5)

515

AH (c8)

569.6

AH (c10)

596

AH (c20)

678

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

1065 – 1364 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

990 – 1064 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Commercial Lighting Inverters, Data Center UPS Systems, Utility Switchgear and Control