Description
Multi-Purpose Long Life Multi-Cell VRLA Battery, Lead Calcium AGM, ABS case, 12V with (2) Threaded M6 Brass Insert terminals [157.4 WPC @15 min to 1.67vpc],[39.5Ah (c10), 35.04Ah (c8)], 11.9″L x 3.8″W x 7.2″H (max ht), 27.6 Lbs
Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate
Multi-Purpose Long Life Multi-Cell VRLA Battery, Lead Calcium AGM, ABS case, 12V with (2) Threaded M6 Brass Insert terminals [157.4 WPC @15 min to 1.67vpc],[39.5Ah (c10), 35.04Ah (c8)], 11.9″L x 3.8″W x 7.2″H (max ht), 27.6 Lbs
| Weight | 27.6 lbs |
|---|---|
| Dimensions | 11.9 × 3.8 × 7.2 in |
| Product Discontinued? | Yes |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead-Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Case Material | ABS |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | Threaded M6 Brass Insert |
| Terminal Location | Front |
| Length inches | 11.9 |
| Width inches | 3.8 |
| Height inches | 7.2 |
| Weight in Lbs | 27.6 |
| WPC (10min to 1.67vpc @ 25c) | 208.9 |
| WPC (15min to 1.67vpc @ 25c) | 157.4 |
| WPC (20min to 1.67vpc @ 25c) | 127.2 |
| 240-cell kW rating (10min) | 50.136 |
| 240-cell kW rating (15min) | 37.776 |
| 240-cell kW rating (20min) | 30.528 |
| AH (c5) | 32.3 |
| AH (c8) | 35.04 |
| AH (c10) | 39.5 |
| Capacity Bracket (10 Min WPC) | 180 – 249 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 130 – 179 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 90 – 129 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 20 – 49 Ah (C8) |
| Capacity Bracket (C8 Ah) | 20 – 49 Ah (C8) |
| Capacity Bracket (C10 Ah) | 20 – 49 Ah (C10) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Telecom, Utility Switchgear and Control |