12V55

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi-Purpose Long Life Multi-Cell VRLA Battery, Lead Calcium AGM, ABS case, 12V with (2) M6 Female terminals [245.3 WPC @15 min to 1.67vpc],[59.8Ah (c10), 58.56Ah (c8)], 10.7″L x 6.5″W x 8.7″H (max ht), 50.5 Lbs

Additional information

Weight 50.5 lbs
Dimensions 10.7 × 6.5 × 8.7 in
Product Discontinued?

Yes

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 Female

Terminal Location

Top

Length inches

10.7

Width inches

6.5

Height inches

8.7

Weight in Lbs

50.5

WPC (10min to 1.67vpc @ 25c)

307.4

WPC (15min to 1.67vpc @ 25c)

245.3

WPC (20min to 1.67vpc @ 25c)

205.9

240-cell kW rating (10min)

73.776

240-cell kW rating (15min)

58.872

240-cell kW rating (20min)

49.416

AH (c5)

55.5

AH (c8)

58.56

AH (c10)

59.8

Capacity Bracket (10 Min WPC)

250 – 324 WPC (10 min)

Capacity Bracket (15 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (20 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control