DDm125-33

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, Polypropylene case, 2V with (6) Threaded Copper Insert terminals per cell [4094 WPC @15 min to 1.67vpc],[2060Ah (c10), 2016Ah (c8)] 12.9″L x 12.9″W x 8.9″H (max ht), 320.3 Lbs

Additional information

Weight 320.3 lbs
Dimensions 12.9 × 12.9 × 8.9 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

12.9

Width inches

12.9

Height inches

8.9

Depth inches

23.5

Weight in Lbs

320.3

WPC (10min to 1.67vpc @ 25c)

4477

WPC (15min to 1.67vpc @ 25c)

4094

WPC (20min to 1.67vpc @ 25c)

3776

240-cell kW rating (10min)

1074.48

240-cell kW rating (15min)

982.56

240-cell kW rating (20min)

906.24

AH (c5)

1850

AH (c8)

2016

AH (c10)

2060

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

4365 – 4664 WPC (10 min)

Capacity Bracket (15 Min WPC)

4065 – 4364 WPC (15 min)

Capacity Bracket (20 Min WPC)

3765 – 4064 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control