2DDm35-07FR

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 4V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, Polypropylene case, 4V with (2) Threaded Copper Insert terminals per cell [292 WPC @15 min to 1.67vpc],[110Ah (c10), 104Ah (c8)] 4.4″L x 4.4″W x 6.5″H (max ht), 42 Lbs

Additional information

Weight 42 lbs
Dimensions 4.4 × 4.4 × 6.5 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

4.4

Width inches

4.4

Height inches

6.5

Depth inches

14.4

Weight in Lbs

42

WPC (10min to 1.67vpc @ 25c)

350

WPC (15min to 1.67vpc @ 25c)

292

WPC (20min to 1.67vpc @ 25c)

250

240-cell kW rating (10min)

84

240-cell kW rating (15min)

70.08

240-cell kW rating (20min)

60

AH (c5)

95

AH (c8)

104

AH (c10)

110

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

325 – 375 WPC (10 min)

Capacity Bracket (15 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control