DDm100-25FR

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Multi Purpose Long Life – Multi Rate single cell VRLA battery used with multi-cell modules, Lead Calcium AGM, Polypropylene case, 2V with (4) Threaded Copper Insert terminals per cell [2394 WPC @15 min to 1.67vpc],[1250Ah (c10), 1208Ah (c8)] 9.9″L x 9.9″W x 6.5″H (max ht), 192.1 Lbs

Additional information

Weight 192.1 lbs
Dimensions 9.9 × 9.9 × 6.5 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

9.9

Width inches

9.9

Height inches

6.5

Depth inches

24.5

Weight in Lbs

192.1

WPC (10min to 1.67vpc @ 25c)

2641

WPC (15min to 1.67vpc @ 25c)

2394

WPC (20min to 1.67vpc @ 25c)

2193

240-cell kW rating (10min)

633.84

240-cell kW rating (15min)

574.56

240-cell kW rating (20min)

526.32

AH (c5)

1105

AH (c8)

1208

AH (c10)

1250

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

2565 – 2864 WPC (10 min)

Capacity Bracket (15 Min WPC)

2265 – 2564 WPC (15 min)

Capacity Bracket (20 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control