12-2DDm35-07 (2-Cell Modules)

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 48V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Cellular Station / SG&C / Solar VRLA Modular Battery String, Lead Calcium AGM, configured as 1 stack of 6 modules, each module w/ (2) VRLA series-connected cells per stackable steel module, Polypropylene case, 48V with (2) Threaded Copper Insert terminals per cell [292 WPC @15 min to 1.67vpc],[110Ah (c10), 104Ah (c8)] 12.78″W x 16.25″D x 60.78″H (max ht), 312 Lbs

Additional information

Weight 312 lbs
Dimensions 12.78 × 12.78 × 60.78 in
Product Discontinued?

No

Availability

Superseded by DDmP equal

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

24

Battery Nominal DC Volts

48

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

12.78

Width inches

12.78

Height inches

60.78

Depth inches

16.25

Weight in Lbs

312

WPC (10min to 1.67vpc @ 25c)

350

WPC (15min to 1.67vpc @ 25c)

292

WPC (20min to 1.67vpc @ 25c)

250

240-cell kW rating (10min)

84

240-cell kW rating (15min)

70.08

240-cell kW rating (20min)

60

AH (c5)

95

AH (c8)

104

AH (c10)

110

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

325 – 375 WPC (10 min)

Capacity Bracket (15 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control