240-DDm125-33 (3-Cell Modules)

Lead-Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 480V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS VRLA Modular Battery String, Lead Calcium AGM, configured as 14 stacks of 6 modules, each module w/ (3) VRLA series-connected cells per stackable steel module, Polypropylene case, 480V with (6) Threaded Copper Insert terminals per cell [4094 WPC @15 min to 1.67vpc],[2060Ah (c10), 2016Ah (c8)] 605.78″W x 27.5″D x 75″H (max ht), 85200 Lbs

Additional information

Weight 85200 lbs
Dimensions 43.27 × 605.78 × 75 in
Product Discontinued?

Yes

Availability

Superseded by DDmP

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

240

Battery Nominal DC Volts

480

Terminal Type

Threaded Copper Insert

Terminal Location

Front

Length inches

43.27

Width inches

605.78

Height inches

75

Depth inches

27.5

Weight in Lbs

85200

WPC (10min to 1.67vpc @ 25c)

4477

WPC (15min to 1.67vpc @ 25c)

4094

WPC (20min to 1.67vpc @ 25c)

3776

240-cell kW rating (10min)

1074.48

240-cell kW rating (15min)

982.56

240-cell kW rating (20min)

906.24

AH (c5)

1850

AH (c8)

2016

AH (c10)

2060

50% DOD Cycle rating

1800

Capacity Bracket (10 Min WPC)

4365 – 4664 WPC (10 min)

Capacity Bracket (15 Min WPC)

4065 – 4364 WPC (15 min)

Capacity Bracket (20 Min WPC)

3765 – 4064 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems