ES-35B (pvc)

Lead-Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

UPS / Switchgear & Control – High Rate Single-Cell Flooded Lead-Acid Battery, Lead Calcium Flat Plate, PVC case, 2V with (4) Square Lead Plated Copper Insert Post terminals [3166 WPC @15 min to 1.67vpc],[1084.8Ah (c8), 1.250 S.G.], 10.1″L x 11.06″W x 18.7″H (max ht), 197.3 Lbs

Additional information

Weight 197.3 lbs
Dimensions 10.1 × 11.06 × 18.7 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead-Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

PVC

Battery Valve Style

Vented

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Square Lead Plated Copper Insert Post

Terminal Location

Top

Length inches

10.1

Width inches

11.06

Height inches

18.7

Weight in Lbs

197.3

WPC (10min to 1.67vpc @ 25c)

3709

WPC (15min to 1.67vpc @ 25c)

3166

WPC (20min to 1.67vpc @ 25c)

2834

240-cell kW rating (10min)

890.16

240-cell kW rating (15min)

759.84

240-cell kW rating (20min)

680.16

AH (c5)

1020

AH (c8)

1084.8

Capacity Bracket (10 Min WPC)

3465 – 3764 WPC (10 min)

Capacity Bracket (15 Min WPC)

3165 – 3464 WPC (15 min)

Capacity Bracket (20 Min WPC)

2565 – 2864 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Utility Switchgear and Control