VR12-150

Lead Acid AGM Pure Lead Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, thin plate pure lead (TPPL) plate

Description

UPS/Telco/Utility/Emergency Lighting GridXtreme VR series battery, Pure Lead AGM, long life in elevated temperatures with robust high rate discharge abilities, ABS-PC case, 12V with (2) M8 threaded insert (M6 adapters optional) terminals [606.9 wpc @ 15min to 1.67vpc, 158Ah (c10) to 1.80vpc @20degC, 163.9Ah (c8) to 1.75vpc @25degC], 14.13″L x 6.85″W x 11.14″H (max ht), 102.7 Lbs

Additional information

Weight 102.7 lbs
Dimensions 14.13 × 6.85 × 11.14 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM Pure Lead

Battery Plate Type

Thin Plate Pure Lead (TPPL)

Case Material

ABS-PC

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 threaded insert (M6 adapters optional)

Terminal Location

Top

Length inches

14.13

Width inches

6.85

Height inches

11.14

Weight in Lbs

102.7

WPC (10min to 1.67vpc @ 25c)

763.6

WPC (15min to 1.67vpc @ 25c)

606.9

WPC (20min to 1.67vpc @ 25c)

508.6

240-cell kW rating (10min)

183.264

240-cell kW rating (15min)

145.656

240-cell kW rating (20min)

122.064

AH (c5)

155.3

AH (c8)

163.9

AH (c10)

167.8

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Elevated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center. Mining, Oil, Telecom, Utility Switchgear and Control