power.com SB 2V 400

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 412 Ah (c8), Regulated Valve, lead calcium grid plate

Description

(Superseded by VRM2-400) UPS/Telco/SG&C/Emergency Lighting Battery, Lead Acid AGM, case, 2V with (4) Composite Threaded Insert terminals [1484.8 WPC @15 min to 1.67vpc],[Ah (c20), 427Ah (c10), 412Ah (c8), S.G.], 7.13″L x 6.06″W x 12.2″H (max ht), 55.1 Lbs

Additional information

Weight 55.1 lbs
Dimensions 7.13 × 6.06 × 12.2 in
Product Discontinued?

Yes

Availability

Superseded by VRM2-400

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Battery Valve Style

Regulated

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

7.13

Width inches

6.06

Height inches

12.2

Weight in Lbs

55.1

WPC (10min to 1.67vpc @ 25c)

1797.7

WPC (15min to 1.67vpc @ 25c)

1484.8

WPC (20min to 1.67vpc @ 25c)

1266.3

240-cell kW rating (10min)

431.448

240-cell kW rating (15min)

356.352

240-cell kW rating (20min)

303.912

AH (c5)

388

AH (c8)

412

AH (c10)

427

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Electric Utility Switchgear Control, Telecom