12V 1 Sun.Power VRL block 70

Lead Acid GEL Medium Cycle – Long Rate Float Service to Moderate Cycling Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium tubular plate

Description

(12V 1 OPzV 70 solar) Solar/Off-Grid Battery, Tubular Plate GEL, case, 12V with (2) Composite Threaded Insert terminals [125.3 WPC @15 min to 1.67vpc],[54Ah (c10), 52Ah (c8), S.G.], 10.7″L x 8.07″W x 15.07″H (max ht), 88.2 Lbs

Additional information

Weight 88.2 lbs
Dimensions 10.7 × 8.07 × 15.07 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

GEL

Battery Plate Type

lead calcium tubular

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

10.7

Width inches

8.07

Height inches

15.07

Weight in Lbs

88.2

WPC (10min to 1.67vpc @ 25c)

142.7

WPC (15min to 1.67vpc @ 25c)

125.3

WPC (20min to 1.67vpc @ 25c)

111.6

240-cell kW rating (10min)

34.248

240-cell kW rating (15min)

30.072

240-cell kW rating (20min)

26.784

AH (c5)

47

AH (c8)

52

AH (c10)

54

50% DOD Cycle rating

2500

Capacity Bracket (10 Min WPC)

130 – 179 WPC (10 min)

Capacity Bracket (15 Min WPC)

90 – 129 WPC (15 min)

Capacity Bracket (20 Min WPC)

90 – 129 WPC (15 min)

Capacity Bracket (C5 Ah)

20 – 49 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Ambient Temp. Resilience

Moderately Elevated

Battery Thermal Mass Level

High

Designed Rate of Discharge

Long-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable