12V 3 power.bloc OPzV 150

Lead Acid GEL Medium Cycle – Long Rate Float Service to Moderate Cycling Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium tubular plate

Description

(Superseded by VRL12-150) Telco/Security/Signalling Battery, Tubular Plate GEL, case, 12V with (2) Composite Threaded Insert terminals [160Ah (c10)], 14.96″L x 8.07″W x 15.07″H (max ht), 163.1 Lbs

Additional information

Weight 163.1 lbs
Dimensions 14.96 × 8.07 × 15.07 in
Product Discontinued?

Yes

Availability

Superseded by VRL12-150

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

GEL

Battery Plate Type

lead calcium tubular

Battery Valve Style

Regulated

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

14.96

Width inches

8.07

Height inches

15.07

Weight in Lbs

163.1

WPC (10min to 1.67vpc @ 25c)

427.5

WPC (15min to 1.67vpc @ 25c)

369.2

WPC (20min to 1.67vpc @ 25c)

325.4

240-cell kW rating (10min)

102.6

240-cell kW rating (15min)

88.608

240-cell kW rating (20min)

78.096

AH (c5)

138

AH (c8)

152.8

AH (c10)

160

Capacity Bracket (10 Min WPC)

376 – 435 WPC (10 min)

Capacity Bracket (15 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (20 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

High

Designed Rate of Discharge

Long-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control