Description
Telco/Security/Solar/Switchgear, DinRef: (12V 3 OPzS 150), Battery, Flooded Tubular Plate, Polypropylene case, 12V with (2) Composite Threaded Insert terminals [150Ah (c10), 1.24 S.G.], 14.96″L x 8.07″W x 15.08″H (max ht), 147.7 Lbs
Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 12V, 0 Ah (c20), Vented or Recombination Valve, lead selenium low antimony tubular plate
Telco/Security/Solar/Switchgear, DinRef: (12V 3 OPzS 150), Battery, Flooded Tubular Plate, Polypropylene case, 12V with (2) Composite Threaded Insert terminals [150Ah (c10), 1.24 S.G.], 14.96″L x 8.07″W x 15.08″H (max ht), 147.7 Lbs
| Weight | 147.7 lbs |
|---|---|
| Dimensions | 14.96 × 8.07 × 15.08 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | Flooded |
| Battery Plate Type | lead selenium low antimony tubular |
| Case Material | Polypropylene |
| Battery Valve Style | Vented or Recombination |
| LOI Rating | UL-94-V0-or-UL-94HB |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | Composite Threaded Insert |
| Terminal Location | Top |
| Length inches | 14.96 |
| Width inches | 8.07 |
| Height inches | 15.08 |
| Weight in Lbs | 147.7 |
| WPC (10min to 1.67vpc @ 25c) | 358.3 |
| WPC (15min to 1.67vpc @ 25c) | 318.9 |
| WPC (20min to 1.67vpc @ 25c) | 287.6 |
| 240-cell kW rating (10min) | 85.992 |
| 240-cell kW rating (15min) | 76.536 |
| 240-cell kW rating (20min) | 69.024 |
| AH (c5) | 137 |
| AH (c8) | 152 |
| AH (c10) | 159 |
| Capacity Bracket (10 Min WPC) | 325 – 375 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 250 – 324 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 250 – 324 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C8 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C10 Ah) | 100 – 199 Ah (C10) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Low |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Medium Cycle |
| Cycling Resilience | Float Service to Moderate Cycling |
| Common Applications | Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control |