VL12-150

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 12V, 0 Ah (c20), Vented or Recombination Valve, lead selenium low antimony tubular plate

Description

Telco/Security/Solar/Switchgear, DinRef: (12V 3 OPzS 150), Battery, Flooded Tubular Plate, Polypropylene case, 12V with (2) Composite Threaded Insert terminals [150Ah (c10), 1.24 S.G.], 14.96″L x 8.07″W x 15.08″H (max ht), 147.7 Lbs

Additional information

Weight 147.7 lbs
Dimensions 14.96 × 8.07 × 15.08 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony tubular

Case Material

Polypropylene

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

14.96

Width inches

8.07

Height inches

15.08

Weight in Lbs

147.7

WPC (10min to 1.67vpc @ 25c)

358.3

WPC (15min to 1.67vpc @ 25c)

318.9

WPC (20min to 1.67vpc @ 25c)

287.6

240-cell kW rating (10min)

85.992

240-cell kW rating (15min)

76.536

240-cell kW rating (20min)

69.024

AH (c5)

137

AH (c8)

152

AH (c10)

159

Capacity Bracket (10 Min WPC)

325 – 375 WPC (10 min)

Capacity Bracket (15 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (20 Min WPC)

250 – 324 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control