11 OPzS1100

Lead Acid Flooded Medium Cycle – Long Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead calcium tubular plate

Description

(Superseded by VL2-1265) Telco/Security/Solar Battery, Flooded Tubular Plate, case, 2V with (4) Composite Threaded Insert terminals [1331Ah (c10)], 8.46″L x 10.9″W x 27.95″H (max ht), 190.9 Lbs

Additional information

Weight 190.9 lbs
Dimensions 8.46 × 10.9 × 27.95 in
Product Discontinued?

Yes

Availability

Superseded by VL2-1265

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium tubular

Battery Valve Style

Vented or Recombination

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

10.9

Height inches

27.95

Weight in Lbs

190.9

WPC (10min to 1.67vpc @ 25c)

2142.1

WPC (15min to 1.67vpc @ 25c)

1983.7

WPC (20min to 1.67vpc @ 25c)

1847.8

240-cell kW rating (10min)

514.104

240-cell kW rating (15min)

476.088

240-cell kW rating (20min)

443.472

AH (c5)

1133

AH (c8)

1276.8

AH (c10)

1331

Capacity Bracket (10 Min WPC)

1965 – 2264 WPC (10 min)

Capacity Bracket (15 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (20 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Long-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Moderate Cycling

Common Applications

Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control