Description
Solar/Security/Switchgear/Telco, DinRef: (9 OPzS 900), Battery, Flooded Tubular Plate, case, 2V with (4) Composite Threaded Insert terminals [1370Ah (c100), 1026Ah (c10), 1.24 S.G.], 8.46″L x 9.25″W x 27.95″H (max ht), 159.6 Lbs
Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Moderate Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium low antimony tubular plate
Solar/Security/Switchgear/Telco, DinRef: (9 OPzS 900), Battery, Flooded Tubular Plate, case, 2V with (4) Composite Threaded Insert terminals [1370Ah (c100), 1026Ah (c10), 1.24 S.G.], 8.46″L x 9.25″W x 27.95″H (max ht), 159.6 Lbs
| Weight | 159.6 lbs |
|---|---|
| Dimensions | 8.46 × 9.25 × 27.95 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0090 |
| Battery Chemistry | Lead Acid |
| Battery Composition | Flooded |
| Battery Plate Type | lead selenium low antimony tubular |
| Battery Valve Style | Vented or Recombination |
| LOI Rating | UL-94-V0-or-UL-94HB |
| Cells per Battery | 1 |
| Battery Nominal DC Volts | 2 |
| Terminal Type | Composite Threaded Insert |
| Terminal Location | Top |
| Length inches | 8.46 |
| Width inches | 9.25 |
| Height inches | 27.95 |
| Weight in Lbs | 159.6 |
| WPC (10min to 1.67vpc @ 25c) | 1753.3 |
| WPC (15min to 1.67vpc @ 25c) | 1623.2 |
| WPC (20min to 1.67vpc @ 25c) | 1512.6 |
| 240-cell kW rating (10min) | 420.792 |
| 240-cell kW rating (15min) | 389.568 |
| 240-cell kW rating (20min) | 363.024 |
| AH (c5) | 927 |
| AH (c8) | 1046 |
| AH (c10) | 1094 |
| Capacity Bracket (10 Min WPC) | 1665 – 1964 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 1365 – 1664 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 1365 – 1664 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 500 – 999 Ah (C8) |
| Capacity Bracket (C8 Ah) | 000 – 1, 1, 999 Ah (C8) |
| Capacity Bracket (C10 Ah) | 000 – 1, 1, 999 Ah (C10) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Low |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Medium Cycle |
| Cycling Resilience | Float Service to Moderate Cycling |
| Common Applications | Industrial Renewable, Mining, Oil, Telecom, Utility Switchgear and Control |