VM2-2140

Lead Acid Flooded Medium Cycle – Medium Rate Float Service to Occasional Cycling Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, lead selenium low antimony grid plate

Description

Premium, Power Plant/UPS/Railway, DinRef: (20 OSP.HC 2100), Battery, Flooded Lead Acid, case, 2V with (6) Composite Threaded Insert terminals [2116Ah (c10), 1.24 S.G.], 8.46″L x 15.75″W x 32.09″H (max ht), 371.9 Lbs

Additional information

Weight 371.9 lbs
Dimensions 8.46 × 15.75 × 32.09 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony grid

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

8.46

Width inches

15.75

Height inches

32.09

Weight in Lbs

371.9

WPC (10min to 1.67vpc @ 25c)

3962.4

WPC (15min to 1.67vpc @ 25c)

3691

WPC (20min to 1.67vpc @ 25c)

3451.2

240-cell kW rating (10min)

950.976

240-cell kW rating (15min)

885.84

240-cell kW rating (20min)

828.288

AH (c5)

1952

AH (c8)

2142.4

AH (c10)

2225

Capacity Bracket (10 Min WPC)

3765 – 4064 WPC (10 min)

Capacity Bracket (15 Min WPC)

3465 – 3764 WPC (15 min)

Capacity Bracket (20 Min WPC)

3165 – 3464 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Medium Cycle

Cycling Resilience

Float Service to Occasional Cycling

Common Applications

Industrial Renewable