VX2-500

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 558.4 Ah (c8), Vented or Recombination Valve, pure lead plante plate

Description

(5 GroE 500) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (2) Composite Threaded Insert terminals [1242.8 WPC @15 min to 1.67vpc],[577Ah (c10), 558.4Ah (c8), 1.22 S.G.], 12.99″L x 10.63″W x 23.23″H (max ht), 209.4 Lbs

Additional information

Weight 209.4 lbs
Dimensions 12.99 × 10.63 × 23.23 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

pure lead plante

Case Material

Translucent Polypropylene

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

12.99

Width inches

10.63

Height inches

23.23

Weight in Lbs

209.4

WPC (10min to 1.67vpc @ 25c)

1390.2

WPC (15min to 1.67vpc @ 25c)

1242.8

WPC (20min to 1.67vpc @ 25c)

1119.7

240-cell kW rating (10min)

333.648

240-cell kW rating (15min)

298.272

240-cell kW rating (20min)

268.728

AH (c5)

515

AH (c8)

558.4

AH (c10)

577

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Electric Utility Switchgear Control