7 GroE 700

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented or Recombination Valve, Pure Lead Flat Plate Plante plate

Description

(Superseded by VX2-700) (7 GroE 700) Premium, Power Plant/Station/UPS Battery, Pure Lead – Planté, 2V with (4) Composite Threaded Insert terminals [1740.3 WPC @15 min to 1.67vpc],[815Ah (c10), 781.6Ah (c8), 1.22 S.G.], 12.99″L x 10.63″W x 23.23″H (max ht), 249.1 Lbs

Additional information

Weight 249.1 lbs
Dimensions 12.99 × 10.63 × 23.23 in
Product Discontinued?

Yes

Availability

Superseded by VX2-700

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

Pure Lead Flat Plate Plante

Battery Valve Style

Vented or Recombination

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Composite Threaded Insert

Terminal Location

Top

Length inches

12.99

Width inches

10.63

Height inches

23.23

Weight in Lbs

249.1

WPC (10min to 1.67vpc @ 25c)

1946.7

WPC (15min to 1.67vpc @ 25c)

1740.3

WPC (20min to 1.67vpc @ 25c)

1567.9

240-cell kW rating (10min)

467.208

240-cell kW rating (15min)

417.672

240-cell kW rating (20min)

376.296

AH (c5)

721

AH (c8)

781.6

AH (c10)

815

Capacity Bracket (10 Min WPC)

1665 – 1964 WPC (10 min)

Capacity Bracket (15 Min WPC)

1665 – 1964 WPC (15 min)

Capacity Bracket (20 Min WPC)

1365 – 1664 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control