XPL8000FT

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 0 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Battery, Lead Calcium AGM, FR polypropylene case, 12V with (2) M6 Threaded Insert terminals [1256 WPC @5 min, 1002 WPC @10 min, 818 WPC @15 min to 1.67vpc, AH (c20), AH (c8)], 21.54″L x 4.94″W x 12.72″H (max ht), 141.72 Lbs

Additional information

Weight 141.72 lbs
Dimensions 21.54 × 4.94 × 12.72 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Polypropylene

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 Threaded Insert

Terminal Location

Front

BCI Reference

FT-SW-190

Length inches

21.54

Width inches

4.94

Height inches

12.72

Weight in Lbs

141.72

WPC (10min to 1.67vpc @ 25c)

1002

WPC (15min to 1.67vpc @ 25c)

818

WPC (20min to 1.67vpc @ 25c)

699

240-cell kW rating (10min)

240.48

240-cell kW rating (15min)

196.32

240-cell kW rating (20min)

167.76

Capacity Bracket (10 Min WPC)

990 – 1064 WPC (10 min)

Capacity Bracket (15 Min WPC)

730 – 819 WPC (15 min)

Capacity Bracket (20 Min WPC)

680 – 729 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems