NSB110FT RED (G1)

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 109.2 Ah (c8), Regulated Valve, pure lead grid plate

Description

(Superseded by NSB110FT HT RED) Telco Battery, Pure Lead AGM (infrequent cycling), elevated temp., high modulus polyphenylene oxide case, 12V with (2) Threaded Insert terminals [453.6 WPC @15 min to 1.67vpc],[118.2Ah (c20), 111.3Ah (c10), 109.2Ah (c8)], 22″L x 4.9″W x 8.9″H (max ht), 86 Lbs

Additional information

Weight 86 lbs
Dimensions 22 × 4.9 × 8.9 in
Product Discontinued?

Yes

Availability

Superseded by NSB110FT HT RED

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

pure lead grid

Case Material

high modulus polyphenylene oxide

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

Threaded Insert

Terminal Location

Front Topside

BCI Reference

FT-SW-100

Length inches

22

Width inches

4.9

Height inches

8.9

Depth inches

22

Weight in Lbs

86

WPC (10min to 1.67vpc @ 25c)

580.4

WPC (15min to 1.67vpc @ 25c)

453.6

WPC (20min to 1.67vpc @ 25c)

375.5

240-cell kW rating (10min)

139.296

240-cell kW rating (15min)

108.864

240-cell kW rating (20min)

90.12

AH (c5)

104.7

AH (c8)

109.2

AH (c10)

111.3

AH (c20)

118.2

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

325 – 375 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Elevated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom