Description
(Discontinued) Telco Battery, Pure Lead AGM (infrequent cycling), elevated temp., high modulus polyphenylene oxide case, 12V with (2) M6 Threaded Insert terminals [13.2Ah (c8)], 6.9″L x 3.2″W x 5.1″H (max ht), 16 Lbs
Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 13.2 Ah (c8), Regulated Valve, pure lead grid plate
(Discontinued) Telco Battery, Pure Lead AGM (infrequent cycling), elevated temp., high modulus polyphenylene oxide case, 12V with (2) M6 Threaded Insert terminals [13.2Ah (c8)], 6.9″L x 3.2″W x 5.1″H (max ht), 16 Lbs
| Weight | 16 lbs |
|---|---|
| Dimensions | 6.9 × 3.2 × 5.1 in |
| Product Discontinued? | Yes |
| Availability | Discontinued |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | pure lead grid |
| Case Material | high modulus polyphenylene oxide |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | M6 Threaded Insert |
| Terminal Location | Top |
| Length inches | 6.9 |
| Width inches | 3.2 |
| Height inches | 5.1 |
| Weight in Lbs | 16 |
| WPC (10min to 1.67vpc @ 25c) | 75.4 |
| WPC (15min to 1.67vpc @ 25c) | 57.7 |
| WPC (20min to 1.67vpc @ 25c) | 47.1 |
| 240-cell kW rating (10min) | 18.096 |
| 240-cell kW rating (15min) | 13.848 |
| 240-cell kW rating (20min) | 11.304 |
| AH (c5) | 12.6 |
| AH (c8) | 13.2 |
| AH (c10) | 13.5 |
| AH (c20) | 14.6 |
| Capacity Bracket (10 Min WPC) | 55 – 89 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 55 – 89 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 38 – 54 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 5 – 19 Ah (C8) |
| Capacity Bracket (C8 Ah) | 5 – 19 Ah (C8) |
| Capacity Bracket (C10 Ah) | 5 – 19 Ah (C10) |
| Capacity Bracket (C20 Ah) | 5 – 19 Ah (C20) |
| Ambient Temp. Resilience | Elevated Temperature |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Telecom |