NSB12-600FT

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 627 watts per cell (15 min), Regulated Valve, thin lead calcium grid plate

Description

(Discontinued) UPS / High Rate Battery, Thin Plate AGM, high modulus polyphenylene oxide case, 12V with (2) M8 Threaded Insert or Male M6 (w/Front Terminal Adapter*) terminals [627 WPC @15 min to 1.67vpc],[Ah (c20), Ah (c10), Ah (c8)], 22″L x 4.9″W x 12.6″H (max ht), 128 Lbs

Additional information

Weight 128 lbs
Dimensions 22 × 4.9 × 12.6 in
Product Discontinued?

Yes

Availability

Discontinued

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

thin lead calcium grid

Case Material

high modulus polyphenylene oxide

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M8 Threaded Insert or Male M6 (w/Front Terminal Adapter*)

Terminal Location

Front Topside

BCI Reference

FT-SW-190

Length inches

22

Width inches

4.9

Height inches

12.6

Depth inches

22

Weight in Lbs

128

WPC (10min to 1.67vpc @ 25c)

792

WPC (15min to 1.67vpc @ 25c)

627

WPC (20min to 1.67vpc @ 25c)

524

240-cell kW rating (10min)

190.08

240-cell kW rating (15min)

150.48

240-cell kW rating (20min)

125.76

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems