Description
General Purpose Battery, Lead Calcium AGM, 12V with (2) Nut/Bolt Flag Post terminals [35Ah (c20)], 7.72″L x 5.14″W x 7″H (max ht), 24.7 Lbs
Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 35 Ah (c20), Regulated Valve, lead calcium grid plate
General Purpose Battery, Lead Calcium AGM, 12V with (2) Nut/Bolt Flag Post terminals [35Ah (c20)], 7.72″L x 5.14″W x 7″H (max ht), 24.7 Lbs
| Weight | 24.7 lbs |
|---|---|
| Dimensions | 7.72 × 5.14 × 7 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Case Material | ABS Resin |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94HB-Non-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | Nut/Bolt Flag Post |
| Terminal Location | Top |
| BCI Reference | U1 |
| Length inches | 7.72 |
| Width inches | 5.14 |
| Height inches | 7 |
| Weight in Lbs | 24.7 |
| WPC (10min to 1.67vpc @ 25c) | 176 |
| WPC (15min to 1.67vpc @ 25c) | 139 |
| WPC (20min to 1.67vpc @ 25c) | 113 |
| 240-cell kW rating (10min) | 42.24 |
| 240-cell kW rating (15min) | 33.36 |
| 240-cell kW rating (20min) | 27.12 |
| AH (c20) | 35 |
| Capacity Bracket (10 Min WPC) | 130 – 179 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 130 – 179 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 90 – 129 WPC (15 min) |
| Capacity Bracket (C20 Ah) | 20 – 49 Ah (C20) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | Medium-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | General Purpose |