Description
UPS / High Rate Battery, Lead Calcium AGM, ABS case, 12V with (2) M6 Threaded Insert terminals [508 WPC @15 min to 1.67vpc],[141.8Ah (c20), 136Ah (c10), 128.8Ah (c8)], 13.58″L x 6.77″W x 10.94″H (max ht), 102 Lbs
Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 141.8 Ah (c20), Regulated Valve, lead calcium grid plate
UPS / High Rate Battery, Lead Calcium AGM, ABS case, 12V with (2) M6 Threaded Insert terminals [508 WPC @15 min to 1.67vpc],[141.8Ah (c20), 136Ah (c10), 128.8Ah (c8)], 13.58″L x 6.77″W x 10.94″H (max ht), 102 Lbs
| Weight | 102 lbs |
|---|---|
| Dimensions | 13.58 × 6.77 × 10.94 in |
| Product Discontinued? | No |
| Availability | Current production line |
| HTS Code | 8507.20.0040 |
| Battery Chemistry | Lead Acid |
| Battery Composition | AGM |
| Battery Plate Type | lead calcium grid |
| Case Material | ABS |
| Battery Valve Style | Regulated |
| LOI Rating | UL-94-V0-Flame-Retardant |
| Cells per Battery | 6 |
| Battery Nominal DC Volts | 12 |
| Terminal Type | M6 Threaded Insert |
| Terminal Location | Top |
| BCI Reference | 31 (tall) |
| Length inches | 13.58 |
| Width inches | 6.77 |
| Height inches | 10.94 |
| Weight in Lbs | 102 |
| WPC (10min to 1.67vpc @ 25c) | 640.34 |
| WPC (15min to 1.67vpc @ 25c) | 508 |
| WPC (20min to 1.67vpc @ 25c) | 410.8 |
| 240-cell kW rating (10min) | 153.6816 |
| 240-cell kW rating (15min) | 121.92 |
| 240-cell kW rating (20min) | 98.592 |
| AH (c5) | 116 |
| AH (c8) | 128.8 |
| AH (c10) | 136 |
| AH (c20) | 141.8 |
| Capacity Bracket (10 Min WPC) | 615 – 679 WPC (10 min) |
| Capacity Bracket (15 Min WPC) | 436 – 524 WPC (15 min) |
| Capacity Bracket (20 Min WPC) | 376 – 435 WPC (15 min) |
| Capacity Bracket (C5 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C8 Ah) | 100 – 199 Ah (C8) |
| Capacity Bracket (C10 Ah) | 100 – 199 Ah (C10) |
| Capacity Bracket (C20 Ah) | 100 – 199 Ah (C20) |
| Ambient Temp. Resilience | Regulated |
| Battery Thermal Mass Level | Medium |
| Designed Rate of Discharge | High-Rate |
| Battery Cycle Class | Float Service Standby |
| Cycling Resilience | limited cycle |
| Common Applications | Data Center UPS Systems |