LHR12600FT

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 600 watts per cell (15 min), Regulated Valve, lead calcium grid plate

Description

UPS High Rate Battery, Advanced AGM VRLA, ABS case, 12V with (2) T11 (Female M8) Front terminals [600 WPC @15 min to 1.67vpc], 21.65″L x 4.92″W x 11.08″H (max ht), 112.43 Lbs

Additional information

Weight 112.43 lbs
Dimensions 21.65 × 4.92 × 11.08 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-or-UL-94HB

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T11 (Female M8)

Terminal Location

Front

Length inches

21.65

Width inches

4.92

Height inches

11.08

Weight in Lbs

112.43

WPC (10min to 1.67vpc @ 25c)

693

WPC (15min to 1.67vpc @ 25c)

600

WPC (20min to 1.67vpc @ 25c)

474

240-cell kW rating (10min)

166.32

240-cell kW rating (15min)

144

240-cell kW rating (20min)

113.76

Capacity Bracket (10 Min WPC)

680 – 729 WPC (10 min)

Capacity Bracket (15 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center, UPS Systems