LHT12-80

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 82.532 Ah (c20), Regulated Valve, high tin lead calcium grid plate

Description

High Temperature Battery, Pure Lead, AGM VRLA, ABS case, 12V with (2) T6 (Female M6) terminals [200.126 WPC @15 min to 1.67vpc],[82.532Ah (c20), 77.174Ah (c10), 73.5456Ah (c8)], 12.05″L x 6.61″W x 8.43″H (max ht), 61.7 Lbs

Additional information

Weight 61.7 lbs
Dimensions 12.05 × 6.61 × 8.43 in
Product Discontinued?

No

Availability

Made to Order

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

high tin lead calcium grid

Case Material

ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

T6 (Female M6)

Terminal Location

Top

Length inches

12.05

Width inches

6.61

Height inches

8.43

Weight in Lbs

61.7

WPC (10min to 1.67vpc @ 25c)

244.024

WPC (15min to 1.67vpc @ 25c)

200.126

WPC (20min to 1.67vpc @ 25c)

172.584

240-cell kW rating (10min)

58.56576

240-cell kW rating (15min)

48.03024

240-cell kW rating (20min)

41.42016

AH (c5)

65.8

AH (c8)

73.5456

AH (c10)

77.174

AH (c20)

82.532

Capacity Bracket (10 Min WPC)

180 – 249 WPC (10 min)

Capacity Bracket (15 Min WPC)

180 – 249 WPC (15 min)

Capacity Bracket (20 Min WPC)

130 – 179 WPC (15 min)

Capacity Bracket (C5 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C8 Ah)

50 – 99 Ah (C8)

Capacity Bracket (C10 Ah)

50 – 99 Ah (C10)

Capacity Bracket (C20 Ah)

50 – 99 Ah (C20)

Ambient Temp. Resilience

Elevated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Mining, Oil, Utility Switchgear and Control, Water Treatment Plant