12FLX540

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 12V, 154 Ah (c20), Regulated Valve, lead calcium grid plate

Description

UPS / High Rate Battery, High Purity Lead Calcium Tin AGM, Thick-Wall ABS case, 12V with (2) 1/4”-20 threaded insert terminals [540 WPC @15 min to 1.67vpc],[154Ah (c20), 136Ah (c8)], 13.31″L x 6.85″W x 10.87″H (max ht), 98 Lbs

Additional information

Weight 98 lbs
Dimensions 13.31 × 6.85 × 10.87 in
Product Discontinued?

Yes

Availability

Discontinued

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Thick-Wall ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

1/4”-20 threaded insert

Terminal Location

Top

BCI Reference

31 (tall)

Length inches

13.31

Width inches

6.85

Height inches

10.87

Weight in Lbs

98

WPC (10min to 1.67vpc @ 25c)

740

WPC (15min to 1.67vpc @ 25c)

540

WPC (20min to 1.67vpc @ 25c)

485

240-cell kW rating (10min)

177.6

240-cell kW rating (15min)

129.6

240-cell kW rating (20min)

116.4

AH (c5)

126

AH (c8)

136

AH (c20)

154

50% DOD Cycle rating

525

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (20 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems