12UMTX170FT

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 12V, 172 Ah (c8), Regulated Valve, lead calcium grid plate

Description

(Superseded by 12FAT170) Telco / Utility / UPS Battery, High Purity Lead Calcium Tin, Thick Grid Plate AGM, Thick Wall ABS case, 12V with (2) M6 Threaded Insert terminals [591.66 WPC @15 min to 1.67vpc],[190Ah (c20), 177Ah (c10), 172Ah (c8), S.G.], 21.97″L x 4.96″W x 12.64″H (max ht), 132 Lbs

Additional information

Weight 132 lbs
Dimensions 21.97 × 4.96 × 12.64 in
Product Discontinued?

Yes

Availability

Superseded by 12FAT170

HTS Code

8507.20.0040

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Thick Wall ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

6

Battery Nominal DC Volts

12

Terminal Type

M6 Threaded Insert

Terminal Location

Front

BCI Reference

FT-SW-190

Length inches

21.97

Width inches

4.96

Height inches

12.64

Weight in Lbs

132

WPC (10min to 1.67vpc @ 25c)

723.99

WPC (15min to 1.67vpc @ 25c)

591.66

240-cell kW rating (10min)

173.7576

240-cell kW rating (15min)

141.9984

AH (c5)

162

AH (c8)

172

AH (c10)

177

AH (c20)

190

50% DOD Cycle rating

550

Capacity Bracket (10 Min WPC)

680 – 729 WPC (10 min)

Capacity Bracket (15 Min WPC)

525 – 614 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C10 Ah)

100 – 199 Ah (C10)

Capacity Bracket (C20 Ah)

100 – 199 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Electric Utility Switchgear Control, Gas Pipeline