2SLA1000

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 1048 Ah (c8), Regulated Valve, lead calcium grid plate

Description

Switchgear & Control Battery, High Purity Lead Calcium Tin, Thick Grid Plate AGM, Thick Wall ABS case, 2V with (4) M12 Threaded Insert terminals [2596 WPC @15 min to 1.67vpc],[1138Ah (c20), 1070Ah (c10), 1048Ah (c8)], 10″L x 20.66″W x 8.26″H (max ht), 162.8 Lbs

Additional information

Weight 162.8 lbs
Dimensions 10 × 20.66 × 8.26 in
Product Discontinued?

No

Availability

FOB Italy Only

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Thick Wall ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

M12 Threaded Insert

Terminal Location

Top

Length inches

10

Width inches

20.66

Height inches

8.26

Weight in Lbs

162.8

WPC (10min to 1.67vpc @ 25c)

2779

WPC (15min to 1.67vpc @ 25c)

2596

WPC (20min to 1.67vpc @ 25c)

2297

240-cell kW rating (10min)

666.96

240-cell kW rating (15min)

623.04

240-cell kW rating (20min)

551.28

AH (c5)

980

AH (c8)

1048

AH (c10)

1070

AH (c20)

1138

50% DOD Cycle rating

550

Capacity Bracket (10 Min WPC)

2565 – 2864 WPC (10 min)

Capacity Bracket (15 Min WPC)

2565 – 2864 WPC (15 min)

Capacity Bracket (20 Min WPC)

2265 – 2564 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000 – 1, 1, 999 Ah (C10)

Capacity Bracket (C20 Ah)

000 – 1, 1, 999 Ah (C20)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Electric Utility Switchgear Control, Telecom