2SLA2000

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 1992 Ah (c8), Regulated Valve, lead calcium grid plate

Description

Switchgear & Control Battery, High Purity Lead Calcium Tin, Thick Grid Plate AGM, Thick Wall ABS case, 2V with (4) M10 Threaded Insert terminals [3688 WPC @15 min to 1.67vpc],[2260Ah (c20), 2050Ah (c10), 1992Ah (c8)], 14.48″L x 25.98″W x 8.58″H (max ht), 314.6 Lbs

Additional information

Weight 314.6 lbs
Dimensions 14.48 × 25.98 × 8.58 in
Product Discontinued?

No

Availability

FOB Italy Only

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

Thick Wall ABS

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

M10 threaded insert

Terminal Location

Top

Length inches

14.48

Width inches

25.98

Height inches

8.58

Weight in Lbs

314.6

WPC (10min to 1.67vpc @ 25c)

4038

WPC (15min to 1.67vpc @ 25c)

3688

WPC (20min to 1.67vpc @ 25c)

3363

240-cell kW rating (10min)

969.12

240-cell kW rating (15min)

885.12

240-cell kW rating (20min)

807.12

AH (c5)

1785

AH (c8)

1992

AH (c10)

2050

AH (c20)

2260

50% DOD Cycle rating

550

Capacity Bracket (10 Min WPC)

3765 – 4064 WPC (10 min)

Capacity Bracket (15 Min WPC)

3465 – 3764 WPC (15 min)

Capacity Bracket (20 Min WPC)

3165 – 3464 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Capacity Bracket (C20 Ah)

000+ Ah (C20), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium

Designed Rate of Discharge

Medium Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Electric Utility Switchgear Control, Telecom