SDH59

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, lead selenium low antimony flat plate

Description

Switchgear / UPS Single Cell Battery, Flooded Lead Selenium, Styrene acrylonitrile (SAN) case, 2V with (6) Lead w/ copper insert terminals [4492 WPC @15 min to 1.67vpc],[2350Ah (c10), 2256Ah (c8), 1.240 S.G.], 17.6″L x 8.6″W x 27.1″H (max ht), 347.6 Lbs

Additional information

Weight 347.6 lbs
Dimensions 17.6 × 8.6 × 27.1 in
Product Discontinued?

No

Availability

FOB Italy Only

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead selenium low antimony flat

Case Material

Styrene acrylonitrile (SAN)

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

Lead w/ copper insert

Terminal Location

Top

Length inches

17.6

Width inches

8.6

Height inches

27.1

Weight in Lbs

347.6

WPC (10min to 1.67vpc @ 25c)

5021

WPC (15min to 1.67vpc @ 25c)

4492

WPC (20min to 1.67vpc @ 25c)

4030

240-cell kW rating (10min)

1205.04

240-cell kW rating (15min)

1078.08

240-cell kW rating (20min)

967.2

AH (c5)

1975

AH (c8)

2256

AH (c10)

2350

Capacity Bracket (10 Min WPC)

5000+ WPC (10 min)

Capacity Bracket (15 Min WPC)

4365 – 4664 WPC (15 min)

Capacity Bracket (20 Min WPC)

3765 – 4064 WPC (15 min)

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C8 Ah)

000+ Ah (C8), 2

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Utility Switchgear and Control