90G15 (High Rate)

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 2V, 700 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte High Rate [connectors sized for 829A or less continuous current are NOT INCLUDED] Multi Purpose VRLA single battery cell used with multicell modules, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 2V, [WPC rates to 1.67 VPC: 1384 WPC @10 min, 1235 WPC @15 min, 1114 WPC @20 min, 1014 WPC @25 min, 932 WPC @30 min, 750 WPC @45 min, 629 WPC @60 min],[608Ah (c8 / 1.75vpc)], 39.69″W x 8.59″H (max ht) x 23.56″D, 106.2 Lbs

Additional information

Weight 106.2 lbs
Dimensions 39.69 × 8.59 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

39.69

Height inches

8.59

Depth inches

23.56

Weight in Lbs

106.2

WPC (10min to 1.67vpc @ 25c)

1384

WPC (15min to 1.67vpc @ 25c)

1235

WPC (20min to 1.67vpc @ 25c)

1114

240-cell kW rating (10min)

332.16

240-cell kW rating (15min)

296.4

240-cell kW rating (20min)

267.36

AH (c5)

550

AH (c8)

608

AH (c10)

640

AH (c20)

700

50% DOD Cycle rating

2500

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems, Telecom, Utility Switchgear and Control