M87-012-05009-R23xxH

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 24V, 240 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 23″ Rack Mount GP Series High Rate [connectors sized for 289A or less continuous current] Cellular Station Modular Battery String configured as 1 stack of 3 modules, ea module w/ (5) VRLA series-connected cells per 23″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 24V, [WPC rates to 1.67 VPC: 573 WPC @10 min, 483 WPC @15 min, 419 WPC @20 min, 373 WPC @25 min, 337 WPC @30 min, 267 WPC @45 min, 224 WPC @60 min],[208Ah (c8 / 1.75vpc)], 24.31″W x 19.47″H (max ht) x 15.15″D, 434.4 Lbs

Additional information

Weight 434.4 lbs
Dimensions 24.31 × 19.47 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

12

Battery Nominal DC Volts

24

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

24.31

Height inches

19.47

Depth inches

15.15

Weight in Lbs

434.4

WPC (10min to 1.67vpc @ 25c)

573

WPC (15min to 1.67vpc @ 25c)

483

WPC (20min to 1.67vpc @ 25c)

419

240-cell kW rating (10min)

137.52

240-cell kW rating (15min)

115.92

240-cell kW rating (20min)

100.56

AH (c5)

185

AH (c8)

208

AH (c10)

220

AH (c20)

240

Capacity Bracket (10 Min WPC)

525 – 614 WPC (10 min)

Capacity Bracket (15 Min WPC)

436 – 524 WPC (15 min)

Capacity Bracket (20 Min WPC)

376 – 435 WPC (15 min)

Capacity Bracket (C5 Ah)

100 – 199 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

200 – 349 Ah (C10)

Capacity Bracket (C20 Ah)

200 – 349 Ah (C20)

Capacity Bracket (C100 Ah)

200 – 349 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control