M87-012-09009-R23xxH

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 24V, 400 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 23″ Rack Mount GP Series High Rate [connectors sized for 423A or less continuous current] Cellular Station Modular Battery String configured as 1 stack of 3 modules, ea module w/ (5) VRLA series-connected cells per 23″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 24V, [WPC rates to 1.67 VPC: 791 WPC @10 min, 706 WPC @15 min, 636 WPC @20 min, 579 WPC @25 min, 532 WPC @30 min, 429 WPC @45 min, 359 WPC @60 min],[344Ah (c8 / 1.75vpc)], 24.31″W x 19.47″H (max ht) x 22.48″D, 722.4 Lbs

Additional information

Weight 722.4 lbs
Dimensions 24.31 × 19.47 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

12

Battery Nominal DC Volts

24

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

24.31

Height inches

19.47

Depth inches

22.48

Weight in Lbs

722.4

WPC (10min to 1.67vpc @ 25c)

791

WPC (15min to 1.67vpc @ 25c)

706

WPC (20min to 1.67vpc @ 25c)

636

240-cell kW rating (10min)

189.84

240-cell kW rating (15min)

169.44

240-cell kW rating (20min)

152.64

AH (c5)

315

AH (c8)

344

AH (c10)

360

AH (c20)

400

Capacity Bracket (10 Min WPC)

730 – 819 WPC (10 min)

Capacity Bracket (15 Min WPC)

680 – 729 WPC (15 min)

Capacity Bracket (20 Min WPC)

615 – 679 WPC (15 min)

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Capacity Bracket (C20 Ah)

350 – 499 Ah (C20)

Capacity Bracket (C100 Ah)

350 – 499 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom, Utility Switchgear and Control