M87-023-09015-R23xxHV

Lead Acid AGM Float Service Standby – High Rate limited cycle Stationary Batteries, 46V, 700 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte 23″ Rack Mount GP Series High Rate [connectors sized for 740A or less continuous current] Telco / Cellular Station Modular Battery String configured as 1 stack of 4 modules, ea module w/ (6) VRLA series-connected cells per 23″ rack-mount stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 46V, [WPC rates to 1.67 VPC: 1384 WPC @10 min, 1235 WPC @15 min, 1114 WPC @20 min, 1014 WPC @25 min, 932 WPC @30 min, 750 WPC @45 min, 629 WPC @60 min],[608Ah (c8 / 1.75vpc)], 24.31″W x 51.92″H (max ht) x 22.48″D, 2293.1 Lbs

Additional information

Weight 2293.1 lbs
Dimensions 24.31 × 51.92 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

23

Battery Nominal DC Volts

46

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

24.31

Height inches

51.92

Depth inches

22.48

Weight in Lbs

2293.1

WPC (10min to 1.67vpc @ 25c)

1384

WPC (15min to 1.67vpc @ 25c)

1235

WPC (20min to 1.67vpc @ 25c)

1114

240-cell kW rating (10min)

332.16

240-cell kW rating (15min)

296.4

240-cell kW rating (20min)

267.36

AH (c5)

550

AH (c8)

608

AH (c10)

640

AH (c20)

700

Capacity Bracket (10 Min WPC)

1365 – 1664 WPC (10 min)

Capacity Bracket (15 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (20 Min WPC)

1065 – 1364 WPC (15 min)

Capacity Bracket (C5 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Telecom