M87-192-09009-048xxM

Lead Acid AGM Float Service Standby – Medium Rate limited cycle Stationary Batteries, 384V, 400 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte GP Series Medium Rate [connectors sized for 215A or less continuous current], (6-90G09 modules), UPS Modular Battery String configured as 4 stacks of 8 modules, ea module w/ (6) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (non FR-rated) case, 384V, [400Ah (c20), 360Ah (c10), 344Ah (c8), 315Ah (c5), 296Ah (c4), 276Ah (c3), 248Ah (c2), 201Ah (c1)], 104.76″W x 68.24″H (max ht) x 23.56″D, 12672 Lbs

Additional information

Weight 12672 lbs
Dimensions 104.76 × 68.24 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (non FR-rated)

Battery Valve Style

Regulated

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

192

Battery Nominal DC Volts

384

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

104.76

Height inches

68.24

Depth inches

23.56

Weight in Lbs

12672

AH (c5)

315

AH (c8)

344

AH (c10)

360

AH (c20)

400

Capacity Bracket (C5 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C8 Ah)

200 – 349 Ah (C8)

Capacity Bracket (C10 Ah)

350 – 499 Ah (C10)

Capacity Bracket (C20 Ah)

350 – 499 Ah (C20)

Capacity Bracket (C100 Ah)

350 – 499 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems