M87-120-09013-037xxUV

Lead Acid AGM Float Service Standby – Ultra High Rate limited cycle Stationary Batteries, 240V, 600 Ah (c20), Regulated Valve, lead calcium grid plate

Description

Absolyte GP Series Ultra-High Rate [connectors sized for 804A or less continuous current], (6-90G13 (FR) modules), UPS / SG&C Modular Battery String configured as 3 stacks of 7 modules, ea module w/ (6) VRLA series-connected cells per stackable steel module, lead calcium tin silver, AGM, polypropylene (FR – flame retardant) case, 240V, [WPC rates to 1.67 VPC: 1342 WPC @5 min, 1186 WPC @10 min, 1059 WPC @15 min, 955 WPC @20 min, 869 WPC @25 min, 799 WPC @30 min, 643 WPC @45 min, 539 WPC @60 min],[520Ah (c8 / 1.75vpc)], 105.57″W x 59.71″H (max ht) x 23.56″D, 11136 Lbs

Additional information

Weight 11136 lbs
Dimensions 105.57 × 59.71 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

AGM

Battery Plate Type

lead calcium grid

Case Material

polypropylene (FR – flame retardant)

Battery Valve Style

Regulated

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

120

Battery Nominal DC Volts

240

Terminal Type

M6 Copper Alloy Threaded Insert

Width inches

105.57

Height inches

59.71

Depth inches

23.56

Weight in Lbs

11136

WPC (10min to 1.67vpc @ 25c)

1186

WPC (15min to 1.67vpc @ 25c)

1059

WPC (20min to 1.67vpc @ 25c)

955

240-cell kW rating (10min)

284.64

240-cell kW rating (15min)

254.16

240-cell kW rating (20min)

229.2

AH (c5)

470

AH (c8)

520

AH (c10)

550

AH (c20)

600

Capacity Bracket (10 Min WPC)

1065 – 1364 WPC (10 min)

Capacity Bracket (15 Min WPC)

990 – 1064 WPC (15 min)

Capacity Bracket (20 Min WPC)

915 – 989 WPC (15 min)

Capacity Bracket (C5 Ah)

350 – 499 Ah (C8)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Capacity Bracket (C10 Ah)

500 – 999 Ah (C10)

Capacity Bracket (C20 Ah)

500 – 999 Ah (C20)

Capacity Bracket (C100 Ah)

500 – 999 Ah (C100)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Medium-High

Designed Rate of Discharge

Ultra High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Commercial Lighting Inverters, Data Center UPS Systems, Utility Switchgear and Control