2-PWQ19-PVC (w/1.215SG)

Lead Acid Flooded Float Service Standby – High Rate limited cycle Stationary Batteries, 4V, 0 Ah (c20), Vented Valve, lead calcium flat plate

Description

PWQ Series High Rate [connectors sized for 2016A or less continuous current], UPS Battery, GNB Flooded Classic, Lead Calcium, PVC case, 4V with (4) Lead Plated Solid Copper terminals [2543 WPC @15 min to 1.67vpc, 965AH (c8), 1.215 S.G.], 12.15″L x 14.5″W x 22.62″H (max ht), 400 Lbs

Additional information

Weight 400 lbs
Dimensions 12.15 × 14.5 × 22.62 in
Product Discontinued?

No

Availability

Current production line

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

lead calcium flat

Case Material

PVC

Battery Valve Style

Vented

LOI Rating

UL-94-V0-Flame-Retardant

Cells per Battery

2

Battery Nominal DC Volts

4

Terminal Type

Lead Plated Solid Copper

Terminal Location

Top

Length inches

12.15

Width inches

14.5

Height inches

22.62

Weight in Lbs

400

WPC (10min to 1.67vpc @ 25c)

2930

WPC (15min to 1.67vpc @ 25c)

2543

WPC (20min to 1.67vpc @ 25c)

2223

240-cell kW rating (10min)

703.2

240-cell kW rating (15min)

610.32

240-cell kW rating (20min)

533.52

AH (c8)

965

Capacity Bracket (10 Min WPC)

2865 – 3164 WPC (10 min)

Capacity Bracket (15 Min WPC)

2265 – 2564 WPC (15 min)

Capacity Bracket (20 Min WPC)

1965 – 2264 WPC (15 min)

Capacity Bracket (C8 Ah)

500 – 999 Ah (C8)

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

High-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Data Center UPS Systems