NVGR022500WC0FA

Lead Acid Flooded Float Service Standby – Medium Rate limited cycle Stationary Batteries, 2V, 0 Ah (c20), Vented Valve, pure lead plante plate

Description

Classic Series (25 GroE 2500) Utility Power Station Battery, Plante’ – flooded, pure lead / long life, 2V cell with (8) M8 Threaded Insert terminals, [1537.5Ah(c1), 2190Ah(c3), 2437.5Ah(c5), 2850Ah(c8) to 1.75vpc], [2675Ah(c10) to 1.80vpc], 12.91″L x 22.56″W x 21.34″H (max ht), 716.5 Lbs.,

Additional information

Weight 716.5 lbs
Dimensions 12.91 × 22.56 × 21.34 in
Product Discontinued?

Yes

Availability

Discontinued

HTS Code

8507.20.0090

Battery Chemistry

Lead Acid

Battery Composition

Flooded

Battery Plate Type

pure lead plante

Case Material

SAN

Battery Valve Style

Vented

LOI Rating

UL-94HB-Non-Flame-Retardant

Cells per Battery

1

Battery Nominal DC Volts

2

Terminal Type

M8 threaded insert

Terminal Location

Top

Length inches

12.91

Width inches

22.56

Height inches

21.34

Weight in Lbs

716.5

AH (c5)

2437.5

AH (c10)

2850

Capacity Bracket (C5 Ah)

000 – 1, 1, 999 Ah (C8)

Capacity Bracket (C10 Ah)

000+ Ah (C10), 2

Ambient Temp. Resilience

Regulated

Battery Thermal Mass Level

Low

Designed Rate of Discharge

Medium-Rate

Battery Cycle Class

Float Service Standby

Cycling Resilience

limited cycle

Common Applications

Power Plant Generating Station, Utility Switchgear and Control